Fault indicator for overhead lines with remote indication and nominal voltages between 5 kV and 138 kV. Complies with IEEE495-207 standard.
Features
Short-circuit Trip Current (Phase to Phase)
50~1200A adjustable, 1A step, 150A default
Earth-fault Voltage Drop (Phase to Ground)
Adjustable: 1% step, 30% default
Earth-fault Response Delay
Adjustable: 1 second step, 30s default
Indication Unit Reset
1. manual by magnet. 2. remote reset through SCADA system 3. time reset: adjustable, 1 second step, 24h default, max. 48h 4. Auto delay reset after repower, 1 second step, 30s default max 5min, only for permanent fault
Protection Class
IP68
Internal Type Test
According to IEEE495-2007
Operation Temperature Range
-40 °C ~ 70 °C
Power Supply
Lithium battery type AA 3.6V / 9Ah, replaceable
Battery Life
10 years
Indicator weight
approx. 590g
DCU weight
approx. 3.6kg
Dimensions
Diameter: 93mm Height: 170mm
Accuracy
0A~300A ±3A 300A~800A ±1%
Cable Diameter Ranges
6mm~42mm
Blinking Frequency
10 per minute, adjustable
Max. load/fault Current
1200A
Voltage range
5~138 kV
Frequency
60Hz
Current withstands
31.5kA/4s
Communication
433MHz from indicators to DCU 2.5G/3G/4G from DCU to SCADA
Communication Protocol
Indicator to DCU: private DCU to SCADA: IEC101, IEC104, DNP3.0, Modbus