Current transformer with rated voltage from 115 kV to 400 kV, according to CFE standard VE100-13. Basic insulation level from 550 kV to 1425 kV. SANDIAN brand.
I am raw html block. Click edit button to change this html
Characteristics
CT 115 kV
CT 138 kV
CT 161 kV
CT 230 kV
CT 400 kV
Rated voltage (kV)
115
138
161
230
400
Max. Design voltage (kV)
123
145
170
245
420
Power frequency Withstand voltage (kV effective)
Internal
230
275
325
460
630
External
230
275
325
460
630
Lightning impulse withstand voltage (kV cresta)
Internal
550
650
750
1050
1425
External
550
650
750
1050
1425
Frequency (Hz)
60
60
60
60
60
Winding 1: measurement class / burden measurement (VA)
0.2S / 30
0.2S / 30
0.2S /30
0.2S / 30
0.2S / 30
Winding 2-3-4: protection class / burden protection (VA)