Metal Oxide Surge arresters for Transmission Substations with nominal voltages from 85 kV up to 230 kV according to CFE VA410-17 specification. Yongde trademark.
Short description | ASOM-III-25-90 | ASOM-III-25-90 | ASOM-III-25-96 | ASOM-III-25-108 | ASOM-III-25-108 | ASOM-III-25-120 | ASOM-III-25-120 | ASOM-III-25-132 | ASOM-III-25-144 | ASOM-III-25-172 | ASOM-III-25-180 | ASOM-III-25-192 |
---|---|---|---|---|---|---|---|---|---|---|---|---|
Rated System Voltage (kV effective) | 85 | 115 | 115 | 115 | 138 | 138 | 161 | 161 | 161 | 230 | 230 | 230 |
Total Length (mm) | 1700 ± 50 | 1700 ± 50 | 1700 ± 50 | 1700 ± 50 | 1700 ± 50 | 1681 ± 50 | 1681 ± 50 | 1700 ± 50 | 1700 ± 50 | 3132 ± 50 | 3133 ± 50 | 3132 ± 50 |
Creepage Distance (mm) | 3150 | 3150 | 3075 | 3075 | 3075 | 3625 | 3625 | 4250 | 4250 | 6300 | 6301 | 6125 |
Surge arresters Rated Voltage Ur (kV effective) | 90 | 90 | 96 | 108 | 108 | 120 | 120 | 132 | 144 | 172 | 180 | 192 |
Continuous Operation Voltage Uc | 70 | 70 | 76 | 84 | 84 | 98 | 98 | 106 | 115 | 138 | 144 | 154 |
Max. Residuals Voltages Switching impulse , 10 kA peak, 1/20µs | 190 | 190 | 200 | 225 | 225 | 250 | 250 | 275 | 317 | 360 | 370 | 390 |
Max. Residuals Voltages Lightning Impulse , 10kA peak, 8/20µs | 222 | 222 | 237 | 268 | 268 | 300 | 300 | 330 | 360 | 430 | 445 | 475 |
Max. Residuals Voltages Steep current Impulse 30/60µs | 260 | 260 | 275 | 310 | 310 | 345 | 345 | 380 | 410 | 500 | 520 | 550 |
Insulated Withstand Voltage Lightning impulse voltage (kV) | 288 | 288 | 308 | 348.4 | 348.4 | 390 | 390 | 429 | 468 | 559 | 578.5 | 507 |
Insulated Withstand Voltage Power Frequency Voltage | 201.4 | 201.4 | 212 | 238.5 | 238.5 | 265 | 265 | 291.5 | 336 | 382 | 393 | 413.4 |
Radio-interference Applied Voltage | 73.5 | 73.5 | 79.8 | 88.2 | 88.2 | 105 | 105 | 111.3 | 121 | 145 | 152 | 162 |
Radio- interferencE Max. (µV) | 2500 | 2500 | 2500 | 2500 | 2500 | 2500 | 2500 | 2500 | 2500 | 2500 | 2500 | 2500 |
Partial Discharge Applied Voltage (kV) | 73.5 | 73.5 | 79.8 | 88.2 | 88.2 | 105 | 105 | 111.3 | 121 | 145 | 152 | 162 |
Partial Discharge Max. Value (pC) | 10 | 10 | 10 | 10 | 10 | 5 | 5 | 10 | 10 | 5 | 5 | 5 |
Short description | ASOM-III-31-90 | ASOM-III-31-96 | ASOM-III-31-108 | ASOM-III-31-120 | ASOM-III-31-132 | ASOM-III-31-144 | ASOM-III-31-172 | ASOM-III-31-180 | ASOM-III-31-192 |
---|---|---|---|---|---|---|---|---|---|
Rated System Voltage (kV effective) | 115 | 115 | 115 | 138 | 161 | 161 | 230 | 230 | 230 |
Total Length (mm) | 1700 ± 50 | 1700 ± 50 | 1700 ± 50 | 1920 ± 50 | 1700 ± 50 | 1701 ± 50 | 3132 ± 50 | 3133 ± 50 | 3095 ± 50 |
Creepage Distance (mm) | 3906 | 3906 | 3906 | 4495 | 5270 | 5270 | 7906 | 7907 | 7595 |
Surge arresters Rated Voltage Ur (kV effective) | 90 | 96 | 108 | 120 | 132 | 144 | 172 | 180 | 192 |
Continious Operation Voltage Uc | 70 | 76 | 84 | 98 | 106 | 115 | 138 | 144 | 154 |
Max. Residuals Voltages Switching impulse , 10 kA peak, 1/20µs | 190 | 200 | 225 | 250 | 275 | 317 | 360 | 370 | 390 |
Max. Residuals Voltages Lightning Impulse , 10kA peak, 8/20µs | 222 | 237 | 268 | 300 | 330 | 360 | 430 | 445 | 475 |
Max. Residuals Voltages Steep current Impulse 30/60µs | 260 | 275 | 310 | 345 | 380 | 410 | 500 | 520 | 550 |
Insulated Withstand Voltage Lightning impulse voltage (kV) | 288 | 308 | 348.4 | 390 | 429 | 468 | 559 | 578.5 | 507 |
Insulated Withstand Voltage Power Frequency Voltage | 201.4 | 212 | 238.5 | 265 | 291.5 | 336 | 382 | 393 | 413.4 |
Radio-interference Applied Voltage | 73.5 | 79.8 | 88.2 | 105 | 111.3 | 121 | 145 | 152 | 162 |
Radio-interference Max. (µV) | 2500 | 2500 | 2500 | 2500 | 2500 | 2500 | 2500 | 2500 | 2500 |
Partial Discharge Applied Voltage (kV) | 73.5 | 79.8 | 88.2 | 105 | 111.3 | 121 | 145 | 152 | 162 |
Partial Discharge Max. Value (pC) | 10 | 10 | 10 | 5 | 10 | 10 | 5 | 5 | 5 |