Unit Capacitive internal fuseless, nominal voltage of 7.96 kV and 13.285 kV, nominal power of 50 kVAr, 100 kVAr, 150 kVAr and 200 kVAr, medium, high and extra high pollution, with two gray porcelain bushings, for an operating altitude up to 2,500 m.a.s.l. According to CFE specification V8000-67. Herong trademark.
Short Description | CP2M-7.96-50-110 | CP2M-7.96-100-110 | CP2M-7.96-150-110 | CP2M-7.96-200-110 | CP2A-7.96-50-110 | CP2A-7.96-100-110 | CP2A-7.96-150-110 | CP2A-7.96-200-110 | CP2E-7.96-50-110 | CP2E-7.96-100-110 | CP2E-7.96-150-110 | CP2E-7.96-200-110 |
---|---|---|---|---|---|---|---|---|---|---|---|---|
Nominal power (kVAr) | 50 | 100 | 150 | 200 | 50 | 100 | 150 | 200 | 50 | 100 | 150 | 200 |
Nominal Voltage between capacitor terminals (kV) | 7.96 | 7.96 | 7.96 | 7.96 | 7.96 | 7.96 | 7.96 | 7.96 | 7.96 | 7.96 | 7.96 | 7.96 |
Normalized lightning impulse withstand voltage (kV) (peak value) for internal – external isolation | 110 | 110 | 110 | 110 | 110 | 110 | 110 | 110 | 110 | 110 | 110 | 110 |
Normalized withstand voltage at 60 Hz (kV) (phase to ground) (r.m.s. value) | 35 | 35 | 35 | 35 | 35 | 35 | 35 | 35 | 35 | 35 | 35 | 35 |
Salinity (test method: salt fog) (kg/m³) | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 |
Nominal Current (A) | 6.28 | 12.56 | 18.84 | 25.13 | 6.28 | 12.56 | 18.84 | 25.13 | 6.28 | 12.56 | 18.84 | 25.13 |
Short Description | CP2M-13.28-50-150 | CP2M-13.28-100-150 | CP2M-13.28-150-150 | CP2M-13.28-200-150 | CP2A-13.28-50-150 | CP2A-13.28-100-150 | CP2A-13.28-150-150 | CP2A-13.28-200-150 | CP2E-13.28-50-150 | CP2E-13.28-100-150 | CP2E-13.28-150-150 | CP2E-13.28-200-150 |
---|---|---|---|---|---|---|---|---|---|---|---|---|
Nominal power (kVAr) | 50 | 100 | 150 | 200 | 50 | 100 | 150 | 200 | 50 | 100 | 150 | 200 |
Nominal Voltage between capacitor terminals (kV) | 13.28 | 13.28 | 13.28 | 13.28 | 13.28 | 13.28 | 13.28 | 13.28 | 13.28 | 13.28 | 13.28 | 13.28 |
Normalized lightning impulse withstand voltage (kV) (peak value) for internal – external isolation | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 |
Normalized withstand voltage at 60 Hz (kV) (phase to ground) (r.m.s. value) | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 |
Salinity (test method: salt fog) (kg/m³) | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 |
Nominal Current (A) | 3.77 | 7.53 | 11.30 | 15.06 | 3.77 | 7.53 | 11.30 | 15.06 | 3.77 | 7.53 | 11.30 | 15.06 |
Power Capacitors without internal fuse nominal voltage 12.27 kV, 13.8 kV and 14.4 kV, nominal power 50 kVAr, 100 kVAr, 150 kVAr and 200 kVAr, medium, high and extra high pollution, with a gray porcelain nozzle, for an altitude of operation up to 2,500 m.a.s.l. according to the CFE V8000-67 specification. Herong brand.
Short Description | CP1M-12.27-50-125 | CP1M-12.27-100-125 | CP1M-12.27-150-125 | CP1M-12.27-200-125 | CP1A-12.27-50-125 | CP1A-12.27-100-125 | CP1A-12.27-150-125 | CP1A-12.27-200-125 | CP1E-12.27-50-125 | CP1E-12.27-100-125 | CP1E-12.27-150-125 | CP1E-12.27-200-125 |
---|---|---|---|---|---|---|---|---|---|---|---|---|
Nominal power (kVAr) | 50 | 100 | 150 | 200 | 50 | 100 | 150 | 200 | 50 | 100 | 150 | 200 |
Nominal Voltage between capacitor terminals (kV) | 12.27 | 12.27 | 12.27 | 12.27 | 12.27 | 12.27 | 12.27 | 12.27 | 12.27 | 12.27 | 12.27 | 12.27 |
Normalized lightning impulse withstand voltage (kV) (peak value) for internal – external isolation | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 |
Normalized withstand voltage at 60 Hz (kV) (phase to ground) (r.m.s. value) | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 |
Salinity (test method: salt fog) (kg/m³) | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 |
Nominal Current (A) | 4.07 | 8.15 | 12.22 | 16.30 | 4.07 | 8.15 | 12.22 | 16.30 | 4.07 | 8.15 | 12.22 | 16.30 |
Short Description | CP1M-13.8-50-110 | CP1M-13.8-100-110 | CP1M-13.8-150-110 | CP1M-13.8-200-110 | CP1A-13.8-50-110 | CP1A-13.8-100-110 | CP1A-13.8-150-110 | CP1A-13.8-200-125 | CP1E-13.8-50-110 | CP1E-12.27-100-110 | CP1E-13.8-150-110 | CP1E-13.8-200-110 |
---|---|---|---|---|---|---|---|---|---|---|---|---|
Nominal power (kVAr) | 50 | 100 | 150 | 200 | 50 | 100 | 150 | 200 | 50 | 100 | 150 | 200 |
Nominal Voltage between capacitor terminals (kV) | 13.8 | 13.8 | 13.8 | 13.8 | 13.8 | 13.8 | 13.8 | 13.8 | 13.8 | 13.8 | 13.8 | 13.8 |
Normalized lightning impulse withstand voltage (kV) (peak value) for internal – external isolation | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 |
Normalized withstand voltage at 60 Hz (kV) (phase to ground) (r.m.s. value) | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 |
Salinity (test method: salt fog) (kg/m³) | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 |
Nominal Current (A) | 3.62 | 7.25 | 10.87 | 14.49 | 3.62 | 7.25 | 10.87 | 14.49 | 3.62 | 7.25 | 10.87 | 14.49 |
Short Description | CP1M-14.4-50-110 | CP1M-14.4-100-110 | CP1M-14.4-150-110 | CP1M-14.4-200-110 | CP1A-14.4-50-110 | CP1A-14.4-100-110 | CP1A-14.4-150-110 | CP1A-14.4-200-125 | CP1E-14.4-50-110 | CP1E-14.4-100-110 | CP1E-14.4-150-110 | CP1E-14.4-200-110 |
---|---|---|---|---|---|---|---|---|---|---|---|---|
Nominal power (kVAr) | 50 | 100 | 150 | 200 | 50 | 100 | 150 | 200 | 50 | 100 | 150 | 200 |
Nominal Voltage between capacitor terminals (kV) | 14.4 | 14.4 | 14.4 | 14.4 | 14.4 | 14.4 | 14.4 | 14.4 | 14.4 | 14.4 | 14.4 | 14.4 |
Normalized lightning impulse withstand voltage (kV) (peak value) for internal – external isolation | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 |
Normalized withstand voltage at 60 Hz (kV) (phase to ground) (r.m.s. value) | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 |
Salinity (test method: salt fog) (kg/m³) | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 |
Nominal Current (A) | 3.47 | 6.94 | 10.42 | 13.89 | 3.47 | 6.94 | 10.42 | 13.89 | 3.47 | 6.94 | 10.42 | 13.89 |